<?xml version="1.0" encoding="UTF-8"?>
<rdf:RDF xmlns="http://purl.org/rss/1.0/" xmlns:rdf="http://www.w3.org/1999/02/22-rdf-syntax-ns#" xmlns:dc="http://purl.org/dc/elements/1.1/">
<channel rdf:about="http://dspace.nbuv.gov.ua:80/handle/123456789/144103">
<title>Електротехніка і електромеханіка, 2015, № 4</title>
<link>http://dspace.nbuv.gov.ua:80/handle/123456789/144103</link>
<description/>
<items>
<rdf:Seq>
<rdf:li rdf:resource="http://dspace.nbuv.gov.ua:80/handle/123456789/149296"/>
<rdf:li rdf:resource="http://dspace.nbuv.gov.ua:80/handle/123456789/149295"/>
<rdf:li rdf:resource="http://dspace.nbuv.gov.ua:80/handle/123456789/149294"/>
<rdf:li rdf:resource="http://dspace.nbuv.gov.ua:80/handle/123456789/149293"/>
</rdf:Seq>
</items>
<dc:date>2026-05-01T17:30:00Z</dc:date>
</channel>
<item rdf:about="http://dspace.nbuv.gov.ua:80/handle/123456789/149296">
<title>Метод визначення спроможності "обмежувача перенапруг нелінійного" поглинати енергію без втрати теплового балансу</title>
<link>http://dspace.nbuv.gov.ua:80/handle/123456789/149296</link>
<description>Метод визначення спроможності "обмежувача перенапруг нелінійного" поглинати енергію без втрати теплового балансу
Шевченко, С.Ю.
На основе экспериментально полученных вольтамперных характеристик варисторов определено напряжение, при&#13;
котором ограничитель перенапряжений нелинейный (ОПН) начинает проводить активный ток, что позволило получить уточненную математическую модель для расчета энергии, которая действует на ОПН и разработать метод&#13;
оценки способности ОПН поддерживать тепловой баланс на протяжении всего срока эксплуатации.; На основі експериментально отриманих вольтамперних характеристик варисторів визначена напруга при якій обмежувач перенапруг нелінійний (ОПН) починає проводити активний струм, що дозволило отримати уточнену математичну модель для розрахунку енергії, що впливає на ОПН та розробити метод оцінювання спроможності ОПН&#13;
підтримувати тепловий баланс на протязі всього строку експлуатації.; Purpose.The aim of this study is to obtain a method for determining the capacity surge arrester nonlinear absorb energy&#13;
without breaking the heat balance in modes of long-term application of operating voltage, which allows for analysis of their&#13;
work in terms of violations as electricity. Methodology. For&#13;
values of the energy passing through the arrester must be able&#13;
to determine the current value for the voltage value in the area&#13;
of leakage current-voltage characteristics. We have carried out&#13;
calculations of the energy passing everywhere arrester for certain periods of time based on the current-voltage characteristics&#13;
obtained experimentally. Analysis of the experimental currentvoltage characteristics of resistors and literature led to the important conclusion that the dielectric properties of the ceramic&#13;
varistor affect the value of active power losses in the arrester&#13;
only when the active component of the leakage current is very&#13;
small. This is confirmed by the characteristics of different&#13;
classes of varistor voltage. This property of varistors and surge&#13;
arresters shows the need to consider how the dielectric and&#13;
conductive properties of the varistor ceramics in the analysis of&#13;
work in the area of the arrester leakage current-voltage characteristic. These results demonstrate the need to clarify the mathematical model and the method for determining the energy dissipates in the area of the arrester leakage current CVC with their&#13;
account. Results. The study, an improved mathematical model&#13;
for calculating energy affects surge arrester during its working&#13;
life. The study obtained the method, of evaluation capacity surge&#13;
arrester, maintains heat balance throughout working life. Based&#13;
on experimentally obtained current-voltage characteristic of the&#13;
varistors is defined voltage at which surge arrester starts conducting active current. This allowed to receive specified mathematical model for calculating energy affects surge arrester and&#13;
develop a method of evaluation capacity surge arrester maintain&#13;
heat balance throughout working life.
</description>
<dc:date>2015-01-01T00:00:00Z</dc:date>
</item>
<item rdf:about="http://dspace.nbuv.gov.ua:80/handle/123456789/149295">
<title>Развитие методов расчета систем тягового электроснабжения и питающих их энергосистем</title>
<link>http://dspace.nbuv.gov.ua:80/handle/123456789/149295</link>
<description>Развитие методов расчета систем тягового электроснабжения и питающих их энергосистем
Доманский, И.В.
Статья посвящена развитию методов расчета систем тягового электроснабжения с учетом питающих их энергосистем. Предложены алгоритмы формализации графов схем внешнего и тягового электроснабжения и методика&#13;
выбора параметров и мест размещения установок продольной компенсации.; Стаття присвячена розвитку методів розрахунку систем тягового електропостачання з урахуванням енергосистем,&#13;
що їх живлять. Запропоновано алгоритми формалізації графів схем зовнішнього і тягового електропостачання та&#13;
методика вибору параметрів і місць розміщення установок поздовжньої компенсації.; Currently, the cause deterioration of quality rating of electricity&#13;
on tire traction substations AC can be either how mode of operation of power systems, industrial loads so and the impact of&#13;
electric traction. The experience of energy surveys show that the&#13;
loss from flow potential equalization currents in each the third&#13;
plot between traction substations AC is amount to not less than&#13;
250 thousand kW·h per year. To select the optimum power and&#13;
places location of the device longitudinal capacitive of compensation and decision other tasks it is necessary methodology of&#13;
systems of calculation that takes into account the complex nature of the mutual influence of the quality of the electricity coming from the energy system of and the transportation process. In&#13;
the paper proposed three options for calculation algorithms&#13;
modes work of existing and perspective systems, traction power&#13;
supply AC jointly with power supply their by energy systems,&#13;
including the algorithm for calculating networks of different&#13;
nominal voltages using the transformations; decomposition and&#13;
synthesis of networks with different voltage levels; the iterations&#13;
and probabilistic assessment of the impact of power mains. Developed the schemes formalization of graphs and the matrices of&#13;
portions of the outer and traction power supply and method of&#13;
selecting parameters and places location of the devices longitudinal capacitive of compensation, which are based on direct&#13;
methods solving systems of linear algebraic equations with a&#13;
dense banded and profile-sparse the matrix. Are generalized&#13;
ways of formation and transformation of graphs of schemes&#13;
traction power supply and feeding them energy systems and&#13;
proposed the method of calculation the complex the moment of&#13;
schemes, which increases the accuracy of calculating of flows&#13;
power on traction networks to 1-2 % and allows you to select&#13;
the optimal parameters and places location of the devices longitudinal capacitive of compensation. Analysis of the results of&#13;
modeling and real modes of traction network shows that the&#13;
efficiency of use longitudinal capacitive compensation is high on&#13;
traction substations for which the resistance external electric&#13;
power supply system of the is greater than 0.5 ohms, and the&#13;
degree of compensation is within the allowable K = 0.7.
</description>
<dc:date>2015-01-01T00:00:00Z</dc:date>
</item>
<item rdf:about="http://dspace.nbuv.gov.ua:80/handle/123456789/149294">
<title>Исследование магнитного поля трехфазных кабельных линий из одножильных кабелей при двустороннем заземлении их экранов</title>
<link>http://dspace.nbuv.gov.ua:80/handle/123456789/149294</link>
<description>Исследование магнитного поля трехфазных кабельных линий из одножильных кабелей при двустороннем заземлении их экранов
Розов, В.Ю.; Квицинский, А.А.; Добродеев, П.Н.; Гринченко, В.С.; Ерисов, А.В.; Ткаченко, А.О.
Исследован процесс ослабления магнитного поля (МП) высоковольтной кабельной линий (КЛ) из одножильных кабелей при двухстороннем заземлении их экранов. Разработана методика численного моделирования и расчета МП КЛ&#13;
на основе метода конечных элементов с применением осесиммеричной расчетной модели КЛ, что позволило описать&#13;
условие замыкания экранов кабелей на концах КЛ и решить задачу в двумерной постановке. Получены точные и экспериментально обоснованные значения коэффициентов ослабления МП КЛ при двустороннем заземлении экранов в&#13;
зависимости от технических характеристик кабелей и геометрии их укладки.; Досліджено процес ослаблення магнітного поля (МП) високовольтної кабельної ліній (КЛ) з одножильних кабелів при&#13;
двосторонньому заземленні їх екранів. Розроблено методику чисельного моделювання та розрахунку МП КЛ на основі&#13;
методу скінченних елементів з застосуванням вісесиметричної розрахункової моделі КЛ, що дозволило описати умову&#13;
замикання екранів кабелів на кінцях КЛ і вирішити задачу в двовимірній постановці. Отримано точні і експериментально обґрунтовані значення коефіцієнтів ослаблення МП КЛ при двосторонньому заземленні екранів в залежності&#13;
від технічних характеристик кабелів.; The study tested the process of the magnetic field (MF) mitigation in the HV three-phase power cable lines (CL) made of single core cables in two-ends bonding of their shields. Developed&#13;
the technique of numerical simulation and calculation of the MF&#13;
of CL based on its axisymmetric calculation model using the&#13;
finite element method that allowed to describe the condition of&#13;
closing the cable shields at the both ends of the CL and solve the&#13;
problem in two-dimensional formulation. The authors show the&#13;
possibility of MF mitigation of the three-phase CL by increasing&#13;
the cross-section of closed cable shields, which in some cases&#13;
may be an alternative to external electromagnetic shields. Obtained and experimentally validated in laboratory and field conditions with an accuracy of no more than 5 % the value of mitigation coefficients of MF of three-phase three-wire CL in twoends bonding of their shields depending on the technical parameters of the cables and the geometry of their installation,&#13;
which is important for the design of new cable power lines.&#13;
Their values are in the range from 0.99 to 0.32 when the cross&#13;
sections of cable shields are from 25 mm2&#13;
 to 200 mm2&#13;
 and the&#13;
distance between the axes of the cables are from 0.1 to 0.5 m.&#13;
The results show the ability to execute design of cable power&#13;
lines in residential areas, taking into account both the sanitary&#13;
standards of the MF, as well as to energy efficiency.
</description>
<dc:date>2015-01-01T00:00:00Z</dc:date>
</item>
<item rdf:about="http://dspace.nbuv.gov.ua:80/handle/123456789/149293">
<title>Экранирование магнитного поля промышленной частоты стенами жилых домов</title>
<link>http://dspace.nbuv.gov.ua:80/handle/123456789/149293</link>
<description>Экранирование магнитного поля промышленной частоты стенами жилых домов
Пелевин, Д.Е.
Проведены экспериментальные исследования эффективности экранирования магнитного поля частотой 50 Гц&#13;
строительными материалами, железобетонными стенами и панельными жилыми домами. Установлено, что магнитное поле частотой 50 Гц практически без ослабления проникает через стены домов, в том числе и железобетонные.; Проведено експериментальні дослідження ефективності екранування магнітного поля частотою 50 Гц будівельними&#13;
матеріалами, залізобетонними стінами і панельними житловими будинками. Встановлено, що магнітне поле частотою 50 Гц практично без ослаблення проникає через стіни будинків в тому числі і залізобетонні.; Purpose. To investigate the effectiveness of the screening of the&#13;
magnetic field at 50 Hz by the walls of house. Methodology. To&#13;
study the effectiveness of the screening we used the measurements of the magnetic field 1) in the area of the shielding screen&#13;
2) in the same area without the shielding screen 3) the calculation of the shielding effectiveness by measuring. Results. We&#13;
have carried out experimental investigations of the effectiveness&#13;
of screening of the magnetic field at 50 Hz by the building materials, concrete walls and paneled houses. Originality. First it is&#13;
experimentally established that the magnetic field with frequency of 50 Hz penetrates through walls of buildings including&#13;
reinforced concrete buildings practically without any decrease.&#13;
Practical value. The results obtained should be considered when&#13;
assessing the hygienic level of the magnetic field in a residential&#13;
area, located near air and cable lines.